Aviemore

Seal-less pump systems · Radford, Virginia

Row CDUs, skids and facility loops  ·  1.0 to 5.0 kW

Row & Facility Pumps

Facility-scale flow, still one part number.

High flow, high head pumps for row-level CDUs, coolant distribution skids, and facility water loops, with the drive electronics integrated across the full 12 to 800 V DC range, not sourced and wired alongside.

Every line shares the same magnetic coupling, the same slotless BLDC motor, and the same integrated drive. What changes between them is the duty, not the architecture. How hydraulic performance gets set for your loop is covered under specifying.

Status
Sampling and limited production

Sampling means units are available for evaluation. Limited production means we are building to order at low volume rather than from stock. It is worth asking what the current output and the next step look like before designing a platform around any supplier.

Power
1.0 to 5.0 kW

Shaft power at the rated duty point. It bounds the range but it is not a selection parameter. Two pumps of the same kilowatt rating can have very different flow and head characteristics depending on impeller geometry and operating speed, which is why duty point rather than power is the thing to specify.

Bus voltage
12 to 800 V DC

The DC supply the drive electronics accept. Data center in-rack distribution has been 54 V DC, and is moving to 800 V DC to keep current manageable as rack power rises. A pump that spans both means the hydraulics survive that transition without qualifying a second supplier.

Drive
AC and DC

Whether the assembly runs from AC distribution, a DC bus, or both. AC suits existing facility power and retrofits; DC suits modern rack architectures. Supporting both is what lets one platform serve a retrofit and a new build.

Typical position
Row CDUs, coolant skids, facility loops

Where in the thermal chain the line normally sits. The chain runs from the facility loop, through a coolant distribution unit, into a rack manifold, and finally to a cold plate on the chip. Flow, head, and redundancy requirements all change at each step.

Coupling
Magnetic, across a sealed containment barrier

Torque is transmitted through a solid containment barrier by magnets on either side of it, with no shaft crossing the boundary. The limit of this arrangement is a maximum transmissible torque: beyond it the two rotors slip out of synchronisation and the impeller stops following the motor.

Insulation
Class B

The thermal class of the winding insulation system, which sets how hot the winding may run continuously. Class A is 105 °C, B is 130 °C, F is 155 °C and H is 180 °C. The relevant figure is the total of ambient plus temperature rise, so a warm coolant loop eats into the margin.

Dynamic seals
None in the fluid path

A dynamic seal is any seal that rides against a moving surface, such as a mechanical face seal or a lip seal on a rotating shaft. It is a sacrificial contact surface and a consumable. Static gaskets and o-rings, which do not move against anything, are a different thing and are still present.

Dry running
Tolerated

Operating with no fluid in the wet end. It happens in practice when a loop is commissioned before it is filled, or when a pump loses prime in service. Many seal-less designs cannot survive it, because the fluid is doing the bearing lubrication or cooling.

Redundancy
N+1, 2N, active-active, hot-swap

N+1 is one spare beyond what the duty requires. 2N is full duplication. Active-active load sharing runs both pumps below rated duty so either can carry the load alone. Hot-swap means a unit can be replaced without taking the loop down. Which one applies is usually set by facility policy, not by the pump.

Country of origin
United States

Where the goods are manufactured, which drives duty treatment, trade-agreement eligibility, and in some cases federal procurement rules such as Buy American provisions.

Where it fits

  • Row CDUs across multiple racks
  • Coolant distribution skids
  • Facility water loops
  • Continuous duty with N+1 or 2N

Get one sized

Send the duty point, the fluid and glycol concentration, the bus voltage available, and the program timeline. An engineer who has built these pumps will answer, and the first reply is technical, not a request for a meeting.

info@aviemoretech.com  · 540-922-9631